% % %

ARMAZENAR/

 

42U Server Rack Cabinet | 600mm Deep Data Center Enclosure

O $800 Decision That Determines Whether Your Servers Overheat, Your Cables Reach, and Your Rack Fits Through the DoorThe rack cabinet is the most underestimated component in a data center deployment. Order the wrong depth and your 800mm-deep GPU servers hang off the back. Order the wrong door and the hot-aisle containment breaks your cooling design. Order the wrong width and the rack does not fit through the server room door. A 42U 600mm-deep rack cabinet — the standard enterprise specification — handles 95 percent of deployments, but the details matter: perforated front and rear doors for airflow, adjustable mounting rails for depth flexibility, cable management rings, and a static load rating of 800-1,000 kg.Technical SpecificationsParameterSpecificationRack Units42U (42 rack units

  • Detalhes do produto

O $800 Decision That Determines Whether Your Servers Overheat, Your Cables Reach, and Your Rack Fits Through the Door

The rack cabinet is the most underestimated component in a data center deployment. Order the wrong depth and your 800mm-deep GPU servers hang off the back. Order the wrong door and the hot-aisle containment breaks your cooling design. Order the wrong width and the rack does not fit through the server room door. A 42U 600mm-deep rack cabinet — the standard enterprise specification — handles 95 percent of deployments, but the details matter: perforated front and rear doors for airflow, adjustable mounting rails for depth flexibility, cable management rings, and a static load rating of 800-1,000 kg.

Especificações técnicas

Parâmetro Especificação
Rack Units 42você (42 rack units of vertical mounting space)
Largura (External) 600 milímetros (19-inch EIA-310 mounting standard)
Profundidade (External) 1,000 milímetros (for 800mm+ server depth)
Altura (External) 2,000 milímetros
Mounting Rails Adjustable front-rear (fits servers from 400mm to 800mm depth)
Front Door Perforated steel, 68 percent open area (airflow optimized)
Rear Door Perforated steel, 68 percent open area
Side Panels Removable, lockable (tool-less removal)
Static Load Rating 1,000 kg (distributed, mounting rails)
Dynamic Load Rating 800 kg (with casters)
Cable Management Rear vertical cable managers (D-rings), horizontal patch panel space
Ventilation Perforated front/rear doors. Optional top fans (2x, for hot-spot relief).
Grounding Grounding studs front and rear (bonding to facility earth)
Physical 2,000 x 600 x 1,000 milímetros, ~120 kg (empty)
Garantia 3-year structural warranty

Rack Cabinet Sizing: The Three Dimensions That Matter

Server Type Server Depth (From Front Flange to Rear) Required Rack Depth Recommended Rack
Standard 2U servers (R660, R760, 2288H V7) ~780mm 1,000mm rack (allows cable management room) 600 x 1000 x 2000mm, 42você
Short 1U edge servers (R470) ~600mm 800mm rack sufficient 600 x 800 x 2000mm, 42você
GPU servers (XE9680, G5500 V7) ~900mm+ (6você, 4U chassis with GPU power) 1,100-1,200mm rack 600 x 1100 x 2000mm (or wider 800mm)
Storage arrays (5288 V7, JBOD) ~800mm 1,000mm rack 600 x 1000 x 2000mm, 42você

Measure your server depth before ordering the rack. A 900mm-deep GPU server requires a 1,100mm+ rack depth. The rear cable management space (the gap between the server rear and the rack rear door) needs at least 150mm for cable bend radius.

Airflow Design: The Perforation Percentage Matters

A rack with solid doors turns into an oven. A rack with 68 percent open-area perforated doors allows natural convection and supports up to 4 kW of air-cooled equipment per rack without forced airflow. For hot-aisle containment designs, the perforated front door draws cold air from the cold aisle and the perforated rear door exhausts into the hot aisle. Solid doors are for immersion-cooled racks or acoustic isolation — not for standard air-cooled servers.

Rack Cabinet Configuration Options

  • Padrão: 42você, 600x1000mm, perforated doors, no fans — covers 90 percent of deployments
  • With Cable Management: Add rear vertical D-ring managers and horizontal cable tray — recommended for any rack with more than 8 servidores
  • With Cooling Fans: Add 2x top-mounted fans (40 CFM each) for hot-spot relief in racks with high-density switches or GPUs
  • With Security: Add front door lock (keyed), rear door lock, and side panel locks for physical security compliance

Source Through Xincuan

We supply 42U rack cabinets with factory-direct pricing, 3-ano de garantia, and global shipping. Configure your rack with cable management, fãs, and security options. Our engineers can help you plan rack layout, power distribution (PDUs), and airflow for your server fleet.

Request a rack cabinet configuration quote

Anterior:

Próximo:

Deixe uma resposta

Telefone +86 18001060290

LinkedIn LinkedIn

Skype +86 18001060290

Whatsapp +86 18001060290

Código QR do WeChat WeChat

E-mail admin@sell-server.com

WeChat

WeChat QR Code

Escaneie o código QR com o WeChat