IL $150 Component That Decides Whether Your 8-GPU Server Turns On
A Dell XE9680 draws 8,500W at peak. A rack PDU rated for 30A at 208V delivers 6,240W. If your PDU is undersized, the server trips the breaker the moment the GPUs hit full load — and the whole rack goes dark, including the servers that were running fine. The APC Basic PDU G2 is the 0U vertical PDU that data center operators install when they need guaranteed power delivery: 30A input, 208v, 20x C13 outlets + 2x C19 outlets, with a 3-meter input cord that runs from the PDU to the rack’s power feed. It is not a smart PDU. It does not monitor. It does not switch. It simply, reliably, delivers power — which is exactly what a $150 power strip replacement should do.
Specifiche tecniche
| Parametro | Specifica |
|---|---|
| Modello | APC Basic PDU G2 (AP9565 or equivalent 30A 0U model) |
| Input | 30UN, 208V single-phase (NEMA L6-30P plug) |
| Output Power Capacity | 6,240W (208V x 30A) |
| Output Outlets | 20x IEC C13 + 2x IEC C19 (C19 for high-wattage servers and PDUs) |
| Fattore di forma | 0U vertical (mounts on rear rail of rack) |
| Vertical Length | 1.8M (fits standard 42U rack height) |
| Input Cord | 3m hardwired, NEMA L6-30P locking plug |
| Breaker | Internal 30A hydraulic-magnetic breaker (trip-free, protects circuit) |
| Mounting | Rear-rail vertical mounting, tool-less with included brackets |
| Physical | 1,828 X 44 X 44 mm (0U), 3.6 kg |
| Temperature | 0C to 45C |
| Garanzia | 2-anno (APC basic PDU warranty) |
PDU Sizing: Match the PDU to the Rack, Not the Other Way Around
| Rack Configuration | Peak Power Draw | Required PDU Rating (208v) | Recommended PDU |
|---|---|---|---|
| 8x R760 (2x 6448Y, 1tubercolosi, 8 Nvme) | ~6 kW | 30UN (6,240W) — 1 PDU per side, 2 totale | APC Basic PDU G2 30A (2X, A/B feed) |
| 4x XE9680 (8x H100 each) | ~34 kW | 60UN (12,480W) — 3x 30A PDUs, or 2x 60A PDU | APC Advanced PDU 60A (smart, metered) x2 |
| Mix: 12x R660 + 2x G5500 V7 | ~18 kW | 60UN (12,480W) — 2x 30A PDU per side | APC Basic PDU G2 30A x4 (2 per side) |
| Edge cabinet (2x R470, 1 switch, 1 UPS) | ~1.5 kW | 15UN (3,120W) — 1 PDU | APC Basic PDU G2 15A (1X) |
Why Every Rack Needs Two PDUs (A/B Feed)
A single PDU is a single point of failure. If it trips, every server plugged into it loses power — regardless of the server’s PSU redundancy. Install two PDUs per rack, each connected to a different power feed (Feed A and Feed B). Connect each server’s PSU1 to Feed A PDU and PSU2 to Feed B PDU. When one PDU trips or a feed fails, every server with dual PSUs continues running on the other feed without a reboot. This is the difference between a 30-second maintenance window and a 3-hour outage with a root-cause analysis meeting.